Project & Applicant Information |
Project Title | Cirkle K Yelm, WA - BG #33080 - 2021 WSEC | For Building Department Use: Date: Nov 11, 2024 |
---|---|---|---|
Project Address | 9548 Killion Rd SE Yelm, WA 98597 |
||
Applicant Name | Sean Stanton | ||
Applicant Phone | 479-636-5004 | ||
Applicant Email | EnergyBG@teamofchoice.com |
Mechanical Compliance Summary Scope - Compliance verification provided in this report is limited to code minimum efficiency requirements for mechanical equipment types defined in Tables C403.3.2(1) through C403.3.2(16) of the 2021 WSEC-C. This includes efficiency multipliers for economizer exceptions. Performance criteria for additional energy efficiency and load management measures ARE NOT included in this report. Additional documentation is required to demonstrate compliance with all other provisions of the energy code, including better than code efficiency criteria for Section C406. For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com.
General Occupancy | All Commercial | General Building Use Type(s) |
Retail, Convenience Store |
Building Cond. Floor Area | 5,192 | ||
---|---|---|---|---|---|---|---|
General Project Types |
New Building
|
New Building or Addition Mechanical Scope |
Single Zone Systems & Equipment
|
Alteration Mechanical Scope |
Project Cond. Floor Area | 5,192 | |
Floors Above Grade | 1 | ||||||
Overall Compliance Path |
General Prescriptive |
||||||
Mechanical Project Description |
Mechanical Compliance Scope and Method |
||||||
---|---|---|---|---|---|---|
Project Type | Mechanical Scope | Economizer Exception(s) Applied? |
DOAS Ventilation Provided? |
Equipment Efficiency Compliance Verification |
||
New Building | Single Zone Systems & Equipment | Yes | Yes | COMPLIES | ||
Additional Energy Efficiency Measures (AEM) |
No mechanical additional energy efficiency measures included in project | Load Management Measures (LDM) |
No mechanical load management measures included in project | |||
Does building include occupancy classifications requiring DOAS? | Yes | Does project include DOAS equipment? | Yes | |||
Based on project scope do TSPR requirements apply? | Yes | Do all systems comply with Appendix D standard reference design or qualify for an exception to TSPR? | Yes |
Scope & Space Conditioning | New Building - Single Zone Systems & Equipment | Compliance Verification | Complies |
---|
Single Zone Air Systems Category - Dedicated outside air system (DOAS) |
---|
Air Systems Summary Information | |||||||
---|---|---|---|---|---|---|---|
System/Equip ID | Paired with other Systems/Equip | Ventilation Airflow Control |
Ventilation Standard | Ventilation CFM | Ventilation energy recovery | Energy Recovery Efficiency (%) |
|
OAU-1 | Paired w/ one single zone system or equipment | Constant volume | IMC Ventilation | 900 | Yes per C403.3.5.1 DOAS ER | 73.15 |
Air Systems & Equipment - Cooling | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
System/ Equip ID |
Cooling System/Equip Type | Specific Type | Cooling Capacity (Btu/h) |
Econo Exception Multiplier (Full) |
Required Cooling Efficiency (Code Min + Econo) |
Proposed Cooling Efficiency |
CE Units |
Efficiency Compliance Verification |
|||
OAU-1 | DX-DOAS, air cooled | With energy recovery | 29,000 | 0 | 5.2 | 6.1 | ISMRE | COMPLIES |
Air Systems & Equipment - Heating | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
System /Equip ID |
Heating System/Equip Type | Specific Type | Heating Output Capacity (Btu/h) |
Heat Pump Heating Capacity (Btu/h) |
Cooling Capacity (Btu/h) (Identical to Cooling Table) |
Required Heat Pump Heating Efficiency |
Proposed Heat Pump Heating Efficiency |
HPH Units |
Efficiency Compliance Verification |
||
OAU-1 | DOAS | Energy recovery ventilator (ERV) | 0 | 0 | 0 | COMPLIES |
Air Systems & Equipment Details | |||||||||
---|---|---|---|---|---|---|---|---|---|
System/Equip ID | Discrete Area(s) Served | Location In Project Documents - Plan/Detail # | System/Equip Compliance Path | ||||||
OAU-1 | 1 | M1.2.1 | General Prescriptive | ||||||
WSEC Equip Efficiency Reference Table - Cooling: Table C403.3.2(12&13) DX-DOAS Units, With & Without ER | |||||||||
Economizer Compliance Method: Air-side economizer provided |
Single Zone Air Systems Category - Heat pump, packaged (PTHP, SPVHP, Room) |
---|
Air Systems Summary Information | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
System/Equip ID | Quantity of Items |
Supply Airflow Control |
Ventilation Standard | Ventilation CFM (Total if Multiple Items) |
Ventilation Air Source |
Paired with DOAS | Ventilation energy recovery | Energy Recovery Efficiency (%) |
|||
RTU1 | Constant volume | IMC Ventilation | 4000 | Integral |
Air Systems & Equipment - Cooling | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
System/ Equip ID |
Cooling System/Equip Type | Specific Type | Cooling Capacity per item (Btu/h) |
Econo Exception Multiplier (Full) |
Required Cooling Efficiency (Code Min + Econo) |
Proposed Cooling Efficiency |
CE Units |
Efficiency Compliance Verification |
|||
RTU1 | Heat pump, terminal (PTHP) | Packaged terminal HP, standard size | 118,000 | 0 | 0 | COMPLIES |
Air Systems & Equipment - Heating | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
System /Equip ID |
Heating System/Equip Type | Specific Type | Heat Pump Heating Capacity per item (Btu/h) |
Cooling Capacity per Item (Btu/h) (Identical to Cooling Table) |
Required Heat Pump Heating Efficiency |
Proposed Heat Pump Heating Efficiency |
HPH Units |
Efficiency Compliance Verification |
|||
RTU1 | Heat pump, terminal (PTHP), heating | Packaged terminal HP, standard size | 115,000 | 118,000 | 0 | COMPLIES |
Air Systems & Equipment Details | |||||||||
---|---|---|---|---|---|---|---|---|---|
System/Equip ID | Discrete Area(s) Served | Location In Project Documents - Plan/Detail # | System/Equip Compliance Path | ||||||
RTU1 | 1 | M1.2.3 | General Prescriptive | ||||||
WSEC Equip Efficiency Reference Table - Cooling: Table C403.3.2(4) Packaged Terminal, Vertical AC & HP and Room AC Units | |||||||||
Economizer Compliance Method: Air-side economizer provided | WSEC Equip Efficiency Reference Table - Heating: Table C403.3.2(4) Packaged Terminal, Vertical AC & HP and Room AC Units |