MECHANICAL COMPLIANCE SUMMARY
2021 WSEC Compliance Forms for Commercial Buildings including Group R1, R2, and Group R3 & R4 over 3 stories Administered by: ©2021 NEEA, All rights reserved
Project & Applicant
Information
Project Title Cirkle K Yelm, WA - BG #33080 - 2021 WSEC For Building Department Use: Date:      Nov 11, 2024
Project Address 9548 Killion Rd SE
Yelm, WA 98597
Applicant Name Sean Stanton
Applicant Phone 479-636-5004
Applicant Email EnergyBG@teamofchoice.com

Mechanical Compliance Summary Scope - Compliance verification provided in this report is limited to code minimum efficiency requirements for mechanical equipment types defined in Tables C403.3.2(1) through C403.3.2(16) of the 2021 WSEC-C. This includes efficiency multipliers for economizer exceptions. Performance criteria for additional energy efficiency and load management measures ARE NOT included in this report. Additional documentation is required to demonstrate compliance with all other provisions of the energy code, including better than code efficiency criteria for Section C406. For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com.

General Occupancy All Commercial General Building Use Type(s) Retail, Convenience Store
Building Cond. Floor Area 5,192
General Project Types
New Building
New Building
or Addition
Mechanical Scope
Single Zone Systems & Equipment
Alteration
Mechanical Scope
Project Cond. Floor Area 5,192
Floors Above Grade 1
Overall Compliance Path General Prescriptive
Mechanical Project Description
Mechanical Compliance
Scope and Method
Project Type Mechanical Scope Economizer Exception(s)
Applied?
DOAS Ventilation
Provided?
Equipment Efficiency
Compliance Verification
New Building Single Zone Systems & Equipment Yes Yes COMPLIES
Additional Energy Efficiency
Measures (AEM)
      No mechanical additional energy efficiency measures included in project Load Management Measures
(LDM)
    No mechanical load management measures included in project
Does building include occupancy classifications requiring DOAS? Yes Does project include DOAS equipment? Yes
Based on project scope do TSPR requirements apply? Yes Do all systems comply with Appendix D standard reference design or qualify for an exception to TSPR? Yes
Scope & Space Conditioning New Building - Single Zone Systems & Equipment Compliance Verification Complies
Single Zone Air Systems Category - Dedicated outside air system (DOAS)
Air Systems Summary Information
System/Equip ID Paired with other Systems/Equip Ventilation Airflow
Control
Ventilation Standard Ventilation CFM Ventilation energy recovery Energy Recovery
Efficiency (%)
OAU-1 Paired w/ one single zone system or equipment Constant volume IMC Ventilation 900 Yes per C403.3.5.1 DOAS ER 73.15
Air Systems & Equipment - Cooling
System/
Equip ID
Cooling System/Equip Type Specific Type Cooling Capacity
(Btu/h)
Econo Exception
Multiplier (Full)
Required Cooling
Efficiency
(Code Min + Econo)
Proposed Cooling
Efficiency
CE
Units
Efficiency Compliance
Verification
OAU-1 DX-DOAS, air cooled With energy recovery 29,000 0 5.2 6.1 ISMRE COMPLIES
Air Systems & Equipment - Heating
System
/Equip ID
Heating System/Equip Type Specific Type Heating Output
Capacity
(Btu/h)
Heat Pump
Heating Capacity (Btu/h)
Cooling Capacity
(Btu/h)
(Identical to
Cooling Table)
Required Heat Pump
Heating Efficiency
Proposed Heat Pump
Heating Efficiency
HPH
Units
Efficiency Compliance
Verification
OAU-1 DOAS Energy recovery ventilator (ERV) 0 0 0 COMPLIES
Air Systems & Equipment Details
System/Equip ID Discrete Area(s) Served Location In Project Documents - Plan/Detail # System/Equip Compliance Path
OAU-1 1 M1.2.1 General Prescriptive
  WSEC Equip Efficiency Reference Table - Cooling: Table C403.3.2(12&13) DX-DOAS Units, With & Without ER  
  Economizer Compliance Method: Air-side economizer provided
Single Zone Air Systems Category - Heat pump, packaged (PTHP, SPVHP, Room)
Air Systems Summary Information
System/Equip ID Quantity
of Items
Supply Airflow
Control
Ventilation Standard Ventilation CFM
(Total if Multiple
Items)
Ventilation
Air Source
Paired with DOAS Ventilation energy recovery Energy Recovery
Efficiency (%)
RTU1 Constant volume IMC Ventilation 4000 Integral
Air Systems & Equipment - Cooling
System/
Equip ID
Cooling System/Equip Type Specific Type Cooling Capacity
per item (Btu/h)
Econo Exception
Multiplier (Full)
Required Cooling
Efficiency
(Code Min + Econo)
Proposed Cooling
Efficiency
CE
Units
Efficiency Compliance
Verification
RTU1 Heat pump, terminal (PTHP) Packaged terminal HP, standard size 118,000 0 0 COMPLIES
Air Systems & Equipment - Heating
System
/Equip ID
Heating System/Equip Type Specific Type Heat Pump
Heating Capacity
per item (Btu/h)
Cooling Capacity
per Item (Btu/h)
(Identical to
Cooling Table)
Required Heat Pump
Heating Efficiency
Proposed Heat Pump
Heating Efficiency
HPH
Units
Efficiency Compliance
Verification
RTU1 Heat pump, terminal (PTHP), heating Packaged terminal HP, standard size 115,000 118,000 0 COMPLIES
Air Systems & Equipment Details
System/Equip ID Discrete Area(s) Served Location In Project Documents - Plan/Detail # System/Equip Compliance Path
RTU1 1 M1.2.3 General Prescriptive
  WSEC Equip Efficiency Reference Table - Cooling: Table C403.3.2(4) Packaged Terminal, Vertical AC & HP and Room AC Units  
  Economizer Compliance Method: Air-side economizer provided WSEC Equip Efficiency Reference Table - Heating: Table C403.3.2(4) Packaged Terminal, Vertical AC & HP and Room AC Units