MECHANICAL COMPLIANCE SUMMARY
2021 WSEC Compliance Forms for Commercial Buildings including Group R1, R2, and Group R3 & R4 over 3 stories Administered by: ©2021 NEEA, All rights reserved
Project & Applicant
Information
Project Title 210 SW Everett Mall Way - 2021 WSEC For Building Department Use: Date:      May 31, 2024
Project Address 210 SW Everett Mall Way
Everett, WA 98208
Applicant Name Alex Burkhart
Applicant Phone 206-763-1744
Applicant Email alexb@evergreenhvac.com

Mechanical Compliance Summary Scope - Compliance verification provided in this report is limited to code minimum efficiency requirements for mechanical equipment types defined in Tables C403.3.2(1) through C403.3.2(16) of the 2021 WSEC-C. This includes efficiency multipliers for economizer exceptions. Performance criteria for additional energy efficiency and load management measures ARE NOT included in this report. Additional documentation is required to demonstrate compliance with all other provisions of the energy code, including better than code efficiency criteria for Section C406. For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com.

General Occupancy All Commercial General Building Use Type(s) Retail, General Sales
Building Cond. Floor Area 10,928
General Project Types
Alteration
New Building
or Addition
Mechanical Scope
Alteration
Mechanical Scope
Single Zone Systems & Equipment
Project Cond. Floor Area 10,928
Floors Above Grade 1
Overall Compliance Path General Prescriptive
Mechanical Project Description
Installation of six (6) replacement rooftop units.
Mechanical Compliance
Scope and Method
Project Type Mechanical Scope Economizer Exception(s)
Applied?
DOAS Ventilation
Provided?
Equipment Efficiency
Compliance Verification
Alteration Single Zone Systems & Equipment Yes No COMPLIES
Additional Energy Efficiency
Measures (AEM)
      No mechanical additional energy efficiency measures included in project Load Management Measures
(LDM)
    No mechanical load management measures included in project
Does building include occupancy classifications requiring DOAS? No Does project include DOAS equipment? No
Based on project scope do TSPR requirements apply? No Do all systems comply with Appendix D standard reference design or qualify for an exception to TSPR? No
Scope & Space Conditioning Alteration - Single Zone Systems & Equipment Compliance Verification Complies
Single Zone Air Systems Category - Air conditioner, split & single package, SC, SDHV
Air Systems Summary Information
System/Equip ID Quantity
of Items
Supply Airflow
Control
Ventilation Standard Ventilation CFM
(Total if Multiple
Items)
Ventilation
Air Source
Paired with DOAS Ventilation energy recovery Energy Recovery
Efficiency (%)
RTU-1 Constant volume IMC Ventilation Integral Not provided, not required
RTU-2 Constant volume IMC Ventilation Integral Not provided, not required
RTU-3 Constant volume IMC Ventilation Integral Not provided, not required
RTU-4 Constant volume IMC Ventilation Integral Not provided, not required
RTU-5 Constant volume IMC Ventilation Integral Not provided, not required
RTU-6 Constant volume IMC Ventilation Integral Not provided, not required
Air Systems & Equipment - Cooling
System/
Equip ID
Cooling System/Equip Type Specific Type Cooling Capacity
per item (Btu/h)
Econo Exception
Multipliers
(Full/IPLV)
Required Cooling
Efficiency
(Code Min + Econo)
Required Part
Load Efficiency
(Code Min + Econo)
Proposed Cooling
Efficiency
CE
Units
Proposed Part
Load Efficiency
PL
Units
Efficiency Compliance
Verification
RTU-1 Air conditioner, air cooled Single package DX 86,000 0 0 11.0 14.6 11 EER 14.6 IEER COMPLIES
RTU-2 Air conditioner, air cooled Single package DX 47,500 0 0 13.4 0 13.4 SEER2 IEER COMPLIES
RTU-3 Air conditioner, air cooled Single package DX 47,500 0 0 13.4 0 13.4 SEER2 IEER COMPLIES
RTU-4 Air conditioner, air cooled Single package DX 47,500 0 0 13.4 0 13.4 SEER2 IEER COMPLIES
RTU-5 Air conditioner, air cooled Single package DX 47,500 0 0 13.4 0 13.4 SEER2 IEER COMPLIES
RTU-6 Air conditioner, air cooled Single package DX 58,500 0 0 13.4 0 13.4 SEER2 IEER COMPLIES
Air Systems & Equipment - Heating
System
/Equip ID
Heating System/Equip Type Specific Type Heat Pump
Heating Capacity (Btu/h)
Cooling Capacity
per Item (Btu/h)
(Identical to
Cooling Table)
Required Heat Pump
Heating Efficiency
Required
Low OSA
Temp Efficiency
Proposed Heat Pump
Heating Efficiency
HPH
Units
Proposed
Low OSA
Temp Efficiency
LTH
Units
Efficiency Compliance
Verification
RTU-1 Furnace Warm air, gas fired (AFUE), weatherized 0 0 COMPLIES
RTU-2 Furnace Warm air, gas fired (AFUE), weatherized 0 0 COMPLIES
RTU-3 Furnace Warm air, gas fired (AFUE), weatherized 0 0 COMPLIES
RTU-4 Furnace Warm air, gas fired (AFUE), weatherized 0 0 COMPLIES
RTU-5 Furnace Warm air, gas fired (AFUE), weatherized 0 0 COMPLIES
RTU-6 Furnace Warm air, gas fired (AFUE), weatherized 0 0 COMPLIES
Air Systems & Equipment Details
System/Equip ID Discrete Area(s) Served Location In Project Documents - Plan/Detail # System/Equip Compliance Path
RTU-1 Retail All General Prescriptive
  Heating Section/Auxiliary Heating Type: Fuel-fired Economizer Compliance Method: Air-side economizer provided
  WSEC Equip Efficiency Reference Table - Cooling: Table C403.3.2(1) Unitary Air Conditioners & Condensing Units  
  WSEC Equip Efficiency Reference Table - Heating:  
RTU-2 Retail All General Prescriptive
  Heating Section/Auxiliary Heating Type: Fuel-fired Economizer Compliance Method: Air-side economizer provided
  WSEC Equip Efficiency Reference Table - Cooling: Table C403.3.2(1) Unitary Air Conditioners & Condensing Units  
  WSEC Equip Efficiency Reference Table - Heating:  
RTU-3 Retail All General Prescriptive
  Heating Section/Auxiliary Heating Type: Fuel-fired Economizer Compliance Method: Air-side economizer provided
  WSEC Equip Efficiency Reference Table - Cooling: Table C403.3.2(1) Unitary Air Conditioners & Condensing Units  
  WSEC Equip Efficiency Reference Table - Heating:  
RTU-4 Retail All General Prescriptive
  Heating Section/Auxiliary Heating Type: Fuel-fired Economizer Compliance Method: Air-side economizer provided
  WSEC Equip Efficiency Reference Table - Cooling: Table C403.3.2(1) Unitary Air Conditioners & Condensing Units  
  WSEC Equip Efficiency Reference Table - Heating:  
RTU-5 Retail All General Prescriptive
  Heating Section/Auxiliary Heating Type: Fuel-fired Economizer Compliance Method: Air-side economizer provided
  WSEC Equip Efficiency Reference Table - Cooling: Table C403.3.2(1) Unitary Air Conditioners & Condensing Units  
  WSEC Equip Efficiency Reference Table - Heating:  
RTU-6 Retail All General Prescriptive
  Heating Section/Auxiliary Heating Type: Fuel-fired Economizer Compliance Method: Air-side economizer provided
  WSEC Equip Efficiency Reference Table - Cooling: Table C403.3.2(1) Unitary Air Conditioners & Condensing Units  
  WSEC Equip Efficiency Reference Table - Heating: